Emerson 2202 Advanced User's Manual page 63

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Parameter
Introduction
x.00
description format
The scaling of the current feedback is based on the ratings of the drive as follows:
Level
Over-current trip
Open-loop peak limit
Open-loop maximum standard operating current
Rated drive current
Maximum Normal Duty current rating
Maximum motor rated current
* On drives that offer dual rating, the rated current can be increased above the rated drive current up to a level not exceeding 1.36 x drive rated
current. The actual level varies from one drive size to another.
The drive has a current controller to give current limiting in frequency control mode and a torque controller in torque control mode. The active current
is controlled by modification of the drive output frequency. Menu 4 provides parameters to set-up the current controller. Additional voltage based
current control is provided to limit transients (peak-limit), but there are no user parameters to control this.
200V
Max
Rated
Heavy
Normal
Model
drive
Duty
current
current
current
rating
rating
2202
17
17
2203
25
25
3201
31
31
3202
42
42
4201
56
56
4202
68
68
4203
80
80
The drive operates in the stator flux reference frame under steady state conditions. The absolute maximum motor current is defined by the peak limit
system as 1.75 x rated drive current. However, the drive does not normally operate at this level, but uses the peak limit system as protection against
over-current trips. Under normal operation the motor current is limited to 1.50 x rated drive current, allowing a safety margin between the maximum
normal operating current and the peak limit level.
DRIVE_CURRENT_MAX is full scale current feedback, i.e. rated drive current x 2.0.
The relationship between the voltage and current is shown in the following vector diagram.
R i
s sx
R i
s sy
v*
i
sy
cos (PF)
ϕ ≈
Commander SK Advanced User Guide
Issue Number: 9
Keypad and
Serial
display
communications
x rated drive current
2.2
1.75
1.5
1.0
≤1.36*
≤1.36*
400V
Max
Max
Rated
Heavy
Duty
Model
drive
Duty
current
current
rating
22
2401
13
13
28
2402
16.5
16.5
42
2403
23
25
54
2404
26
26
68
3401
32
32
80
3402
40
40
104
3403
46
46
4401
60
60
4402
74
74
4403
96
96
5401
124
124
5402
156
156
6401
154.2
180
6402
180
210
-1
Stator flux
(in steady state)
www.controltechniques.com
CT Modbus
PLC Ladder
CTSoft
RTU
programming
575V
Max
Max
Normal
Rated
Heavy
Duty
Model
drive
Duty
current
current
current
rating
rating
15.3
3501
4.1
4.1
21
3502
5.4
5.4
29
3503
6.1
6.1
29
3504
9.5
9.5
35
3505
12
12
43
3506
18
18
56
3507
22
22
68
83
104
138
168
205
236
Advanced parameter
Menu 0
descriptions
690V
Max
Max
Normal
Rated
Heavy
Duty
Model
drive
Duty
current
current
current
rating
rating
5.4
4601
19
19
6.1
4602
22
22
8.4
4603
27
27
11
4604
36
36
16
4605
43
43
22
4606
52
52
27
5601
63
63
5602
85
85
6601
85.7
100
6602
107.1
125
Menu 4
Max
Normal
Duty
current
rating
22
27
36
43
52
62
84
99
125
144
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents