Trip Indications - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Menu 10
Introduction
x.00
Table 10-17 Trip indications
No.
String
1
UU***
DC bus under voltage - Low AC supply voltage. Low DC Bus voltage when drive supplied by external DC power supply.
DC bus over voltage.
Drive voltage rating
2
OU
Excessive inertia in the machine during deceleration. Deceleration rate is set too fast for inertia of machine.
AC instantaneous over current. Insufficient ramp times. Phase to phase or phase to ground short circuit at the drive
3
OI.AC**
output. Autotune required.
4
OI.br**
Braking resistor instantaneous current trip. Excessive current in braking resistor. Braking resistor value too small.
6
Et
External trip (see Pr 10.32 on page 136)
Overspeed. Excessive motor speed (typically caused by the mechanical load driving the motor). The drive produces an
7
O.SPd
overspeed trip if the output frequency (Pr 5.01) exceeds 1.2 x Maximum frequency and regenerating and in current limit.
18
tunE
Auto-tune stopped before completion (see Pr 5.12 on page 77)
2
19
It.br
I
t on braking resistor (see Pr 10.31 on page 135)
2
20
It.AC
I
t on drive output current (see Pr 4.15 on page 68)
21
O.ht1
Drive over-heat (IGBT junctions) based on thermal model (see Pr 5.18 on page 80)
22
O.ht2
Drive over-heat based on heatsink temperature (see Pr 7.04 on page 103)
24
th
Motor thermistor trip
26
O.Ld1*
+24V or Digital output overload
Drive over-heat based on thermal model (see Pr 7.35 on page 108)
The drive will attempt to stop the motor before tripping. If the motor does not stop in 10 seconds the drive trips
27
O.ht3
immediately. Thermal model looks at DC Bus ripple as well as output current. This is to protect the DC Bus stage from
overheating.
28
cL1
Analog input 1 current mode: current loss (see Pr 7.06 on page 104)
30
SCL
Serial comms timeout with external keypad on drives comms port
Internal drive EEPROM failure. All the parameters are set to default. The trip can only be removed by entering a load
31
EEF
default command (see Pr 11.43 on page 149)
High input voltage phase imbalance or input phase loss. Normally a motor load of between 50 and 100% of drive rating is
32
PH
required to trigger the trip. The drive will attempt to stop the motor before tripping. The drive looks at DC Bus ripple.
Failure to measure stator resistance during auto-tune or when starting in open-loop voltage modes 0 or 3. This is either
33
rS
because the resistance exceeds the maximum measurable value or no motor connected to drive (see Pr 5.12 on page 77,
Pr 5.14 and Pr 5.17 on page 80)
35
CL.bt
Trip initiated from the control word (see Pr 6.42 on page 99)
t040 -
40-89
User trips
t089
90
t090
PLC ladder program attempted divide by zero
91
t091
PLC ladder program attempted access to non-existent parameter
92
t092
PLC ladder program attempted write to a read only parameter
94
t094
PLC ladder program attempted to write a value to a parameter which is out of range
95
t095
PLC ladder program virtual memory stack overflow
96
t096
PLC ladder program invalid operating system call
97
t097
PLC ladder program enabled with no LogicStick inserted or LogicStick removed
98
t098
PLC ladder program invalid instruction
99
t099
PLC ladder program invalid function block argument
100
Drive reset (see Pr 10.38 on page 137)
102
O.ht4
Power module rectifier over temperature. Check for supply imbalance. Increase acceleration/deceleration rates.
Data does not exist:
183
C.dAt
An attempt has been made to transfer data from a blank SmartStick or data block that does not exist or verify after write
fail.
SmartStick read/write fail:
185
C.Acc
The drive cannot communicate with the SmartStick either because it is faulty or is not installed in the drive. Removing a
stick during an access will cause this trip.
Rating change:
186
C.rtg
The parameters loaded to the drive from a SmartStick are for a drive of a different voltage or current rating. No rating
dependent parameters have been transferred.
189
O.cL
Overload on current loop input (analog input 1).
199
dESt
Destination parameter clash
Solutions Module hardware fault. This could occur because the module cannot be identified, or the module has not
200
SL.HF
indicated it is running within 5s of drive power-up, or an internal hardware fault has occurred in the module.
Solutions Module watchdog timeout. The module has started the watchdog system, but has not subsequently serviced the
201
SL.tO
watchdog within the timeout period.
132
Parameter
Keypad and
description format
display
Instantaneous trip
200V
415V
400V
830V
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
communications
RTU
programming
Cause of trip
Advanced parameter
CTSoft
Menu 0
descriptions
Commander SK Advanced User Guide
Issue Number: 9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents