Menu 9: Programmable Logic, Motorized Pot And Binary Sum - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Menu 9
Introduction
x.00
10.10

Menu 9: Programmable logic, motorized pot and binary sum

Table 10-15 Menu 9 parameters: single line descriptions
Parameter
9.01
Logic function 1 output
9.02
Logic function 2 output
9.03
Motorized pot output
9.04
Logic function 1 source 1
9.05
Logic function 1 source 1 invert
9.06
Logic function 1 source 2
9.07
Logic function 1 source 2 invert
9.08
Logic function 1 output invert
9.09
Logic function 1 delay
9.10
Logic function 1 destination
9.11
Not used
9.12
Not used
9.13
Not used
9.14
Logic function 2 source 1
9.15
Logic function 2 source 1 invert
9.16
Logic function 2 source 2
9.17
Logic function 2 source 2 invert
9.18
Logic function 2 output invert
9.19
Logic function 2 delay
9.20
Logic function 2 destination
9.21
Motorized pot mode
9.22
Motorized pot bipolar select
9.23
Motorized pot rate
9.24
Motorized pot scale factor
9.25
Motorized pot destination
9.26
Motorized pot up
9.27
Motorized pot down
9.28
Motorized pot reset
9.29
Binary sum one's input
9.30
Binary sum two's input
9.31
Binary sum four's input
9.32
Binary sum output
9.33
Binary sum destination
9.34
Binary sum offset
118
Parameter
Keypad and
description format
display
communications
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
RTU
programming
Range
OFF(0) or On(1)
OFF(0) or On(1)
±100.0%
Pr 0.00 to Pr 21.51
OFF(0) or On(1)
Pr 0.00 to Pr 21.51
OFF(0) or On(1)
OFF(0) or On(1)
±25.0 s
Pr 0.00 to Pr 21.51
Pr 0.00 to Pr 21.51
OFF(0) or On(1)
Pr 0.00 to Pr 21.51
OFF(0) or On(1)
OFF(0) or On(1)
±25.0 s
Pr 0.00 to Pr 21.51
0 to 3
OFF(0) or On(1)
0 to 250 s
0.000 to 4.000
Pr 0.00 to Pr 21.51
OFF(0) or On(1)
OFF(0) or On(1)
OFF(0) or On(1)
OFF(0) or On(1)
OFF(0) or On(1)
OFF(0) or On(1)
0 to 255
Pr 0.00 to Pr 21.51
0 to 248
Advanced parameter
CTSoft
Menu 0
descriptions
Default
Setting
Pr 0.00
OFF(0)
Pr 0.00
OFF(0)
OFF(0)
0.0
Pr 0.00
Pr 0.00
OFF(0)
Pr 0.00
OFF(0)
OFF(0)
0.0
Pr 0.00
2
OFF(0)
20
1.000
Pr 0.00
OFF(0)
OFF(0)
OFF(0)
OFF(0)
OFF(0)
OFF(0)
Pr 0.00
0
Commander SK Advanced User Guide
Issue Number: 9
Update Rate
21 ms
21 ms
21 ms
Drive reset
21 ms
Reset
21 ms
21 ms
21 ms
Drive reset
Drive reset
21 ms
Drive reset
21 ms
21 ms
21 ms
Drive reset
BR
21 ms
B
B
Drive reset
21 ms
21 ms
21 ms
21 ms
21 ms
21 ms
21 ms
Drive reset
21 ms

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents