Terminals T5 to T7 are three programmable digital inputs.
These parameters indicate the state of the digital input terminals.
If an external trip is required, then one of the terminals should be programmed to control the external trip parameter (Pr 10.32), with the invert set to
On(1) so that the terminal must be made active for the drive not to trip.
NOTE
The digital inputs are set up in positive logic. This logic cannot be changed.
15.07
Relay 1 state (Terminals T21 and T23)
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background write
0: OFF De-energized
1: On
Energized
This parameter indicates the state of the relay.
15.08 to 15.13
Unused parameters
15.14
Terminal T5 digital input 1 invert
15.15
Terminal T6 digital input 2 invert
15.16
Terminal T7 digital input 3 invert
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
Background read
Setting these parameters to On(1) causes the input sense to the destination parameter to be inverted.
15.17
Relay 1 invert (terminals T21 and T23)
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
Background read
Setting this parameter to On(1) causes the relay sense to be inverted.