Modbus Rtu / User Serial Mode; Serial Comms Baud Rate; Silent Period Extension; Drive Configuration - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Menu 11
Introduction
x.00
Address 0 is used to globally address all slaves, and so this address should not be set in this parameter.
The communications port on the Commander SK will support Modbus RTU protocol only. Full details of the CT implementation of Modbus RTU are
given in "CT MODBUS RTU specification".
The protocol provides the following facilities:
Drive parameter access with basic Modbus RTU
Drive parameter database upload via CMP extensions
The following product specific limitations apply:
Maximum slave response time when accessing the drive is 100ms
Maximum number of 16 bit registers that can be written to, or read from, the drive itself is limited to 16
The communications buffer can hold a maximum of 128 bytes
11.24

Modbus RTU / user serial mode

Bit
SP
Coding
Range
0 to 3
Default
1
Update rate
Background
Modes 0, 1 and 4 are for Modbus slave mode. Modes 2 and 3 allow a drive user program to control the comms.
0: mode 0
8 data bits and 1 stop bit with no parity (Commander SE backward compatibility)
1: mode 1
8 data bits and 2 stop bits with no parity
2: mode 2
7 data bits and 1 stop bit with even parity
3: mode 3
8 data bits and 2 stop bits with no parity
4: mode 4
8 data bits and 1 stop bit with even parity
11.25

Serial comms baud rate {43}

Bit
SP
Coding
Range
2.4(0), 4.8(1), 9.6(2), 19.2(3), 38.4(4),
Default
19.2(3)
Update rate
Background
This parameter is used to select the comms port baud rate in kilo baud.
11.26

Silent period extension

Bit
SP
Coding
Range
0 to 250 ms
Default
2
Update rate
Background
Modbus RTU uses a silent period detection system to detect the end of a message. This silent period is normally the length of time for 3.5 characters
at the present baud rate, but for systems that cannot turn the communications buffers around fast enough this time can be extended to the time
programmed in Pr 11.26.
11.27

Drive configuration {05}

Bit
SP
Coding
Range
AI.AV(0), AV.Pr(1), AI.Pr(2), Pr(3), PAd(4), E.Pot(5), tor(6), Pid(7), HVAC(8)
Default
Eur: AI.AV(0), USA: PAd(4)
Update rate
Actioned on exit of edit mode or drive reset.
This parameter is used to automatically set up the user programmable area in the level 3 parameter set according to the required drive configuration.
Other default parameters may also be changed automatically by the drive configuration. See Table 10-23 for drive configuration parameter changes.
A change to Pr 11.27 is set on the exit of parameter edit mode or on a drive reset. The drive must be disabled, stopped or tripped for a change to take
place. If Pr 11.27 is changed while the drive is running, the parameter will return to its pre-altered value. Following a drive configuration change, the
parameters are automatically stored in EEPROM.
In all of the following settings, the status relay is set up as a drive ok relay.
T5
OK
Fault
T6
140
Parameter
Keypad and
description format
display
FI
DE
Txt VM DP
ND
FI
DE
Txt VM DP
ND
1
FI
DE
Txt VM DP
ND
FI
DE
Txt VM DP
ND
1
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
communications
RTU
programming
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
1
Advanced parameter
CTSoft
Menu 0
PS
1
PS
1
PS
1
PS
1
Commander SK Advanced User Guide
Issue Number: 9
descriptions