Parameter
Menu 7
Introduction
x.00
7.11

Analog input 2 mode (terminal T4)

Bit
SP
Coding
Range
VoLt(0) or dig(1)
Default
VoLt(0)
Update rate
Background
Analog input 2 can be configured as either a 0 to +10V analog input or a +24V digital input (positive logic).
Value
Display
0
VoLt
1
dig
7.12

Analog input 2 scaling

Bit
SP
Coding
Range
0.000 to 4.000
Default
1.000
Update rate
Background
When analog input 2 is set up for analog input, this parameter is used to scale the input (see Pr 7.08). When the input is defined as a digital input, this
parameter has no effect.
7.13
Analog input 2 invert
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
5 ms
When set-up as an analog input, this parameter can be used to invert the analog input reference (i.e. multiply the input scaling result by -1).
For digital input, this parameter selects a digital inversion.
7.14
Analog input 2 destination
Bit
SP
Coding
Range
Pr 0.00 to Pr 21.51
Default
Pr 1.37
Update rate
Read on drive reset
As default, this parameter is set-up automatically according to the drive configuration (see Pr 11.27 on page 140).
Only parameters which are not protected can be controlled by analog inputs. If a non valid parameter is programmed to the destination of an analog
input, the input is not routed anywhere.
After a modification to this parameter, the destination is only changed when a reset is performed.
7.15 to 7.18
Unused parameters
7.19

Analog output source

Bit
SP
Coding
Range
Pr 0.00 to Pr 21.51
Default
Pr 2.01
Update rate
Read on drive reset
The parameter required to be represented as an analog signal by the analog output on terminal B1, should be programmed in this parameter.
This parameter is used in conjunction with Pr 7.33 to determine the analog output signal. Pr 7.33 has 4 pre-determined settings for easy set-up of the
analog output. If the user requires to set Pr 7.19 to another parameter, then Pr 7.33 must be set to 4: USEr.
See Pr 7.33 for further details. If a non valid parameter is programmed as a source, the output will remain at zero.
106
Parameter
Keypad and
description format
display
FI
DE
Txt VM DP
ND
1
Function
0 to +10V
0 to +24V
FI
DE
Txt VM DP
ND
3
FI
DE
Txt VM DP
ND
FI
DE
Txt VM DP
ND
1
2
FI
DE
Txt VM DP
ND
2
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
communications
RTU
programming
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
1
RA NC
NV
PT
US RW BU
1
1
1
Advanced parameter
CTSoft
Menu 0
PS
1
PS
1
PS
PS
1
PS
1
Commander SK Advanced User Guide
Issue Number: 9
descriptions