Analog Input 1 Destination (Terminal T2); Analog Output 1 Source (Terminal T3); Analog Output 1 Scaling (Terminal T3); Solutions Module Error Status - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Menu 15
Parameter
Introduction
I/O options
x.00
15.43

Analog input 1 destination (Terminal T2)

Bit
SP
Coding
Range
Pr 0.00 to Pr 21.51
Default
Pr 0.00
Update rate
Drive read on reset
Only parameters that are not protected can be controlled by analog inputs. If a non-valid parameter is programmed to the destination of an analog
input, the input is not routed anywhere. After a modification to this parameter, the destination is only changed when a reset is performed.
15.44 to 15.47
Unused parameters
15.48

Analog output 1 source (Terminal T3)

Bit
SP
Coding
Range
Pr 0.00 to Pr 21.51
Default
Pr 0.00
Update rate
Drive read on reset
The parameter required to be represented as an analog signal by the analog output on Terminal T3 should be programmed in this parameter. Only
parameters that are valid can be programmed as a source. If a non-valid parameter is programmed as a source, the output will remain at zero. After
a modification to this parameter, the source is only changed when a reset is performed.
15.49

Analog output 1 scaling (Terminal T3)

Bit
SP
Coding
Range
0.000 to 4.000
Default
1.000
Update rate
Background read
This parameter can be used to scale the analog output if so desired. However in most cases it is not necessary as the output is automatically scaled
such that when the source parameter is at its maximum, the analog output will be at its maximum.
15.50

Solutions Module error status

Bit
SP
Coding
Range
0 to 255
Update rate
Background write
If a Solutions Module error is detected, the drive will trip on SL.Er. The reason for the trip is stored in Pr 15.50.
Table 10-28 Error Codes
Error Code
0
No error
1
Digital output short circuit
2
Current input to high or too low
3
Encoder supply over current
4
SM-I/O Lite / SM-I/O Timer serial communications error
5
Real time clock error (SM-I/O Timer only)
74
SM-I/O Lite / SM-I/O Timer PCB over temperature
The drive can also trip on a number of Solutions Module trips, SL.xx. Please see table 9-13, Trip Indications in the Commander SK Advanced User
Guide.
The SM-I/O Lite and SM-I/O Timer includes a temperature monitoring circuit. If the pcb temperature exceeds 65°C, the drives cooling fan is forced to
operate for a minimum of 20 seconds. If the pcb temperature falls below 65°C, the fan will switch off. If the pcb temperature exceeds 70°C, the drive
will trip on SL.Er and the error status will be set to 74.
182
Parameter
Keypad and
description format
display
FI
DE
Txt VM DP
ND
2
FI
DE
Txt VM DP
ND
2
FI
DE
Txt VM DP
ND
3
FI
DE
Txt VM DP
ND
1
Reason for Fault
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
communications
RTU
programming
RA NC
NV
PT
US RW BU
1
1
1
RA NC
NV
PT
US RW BU
1
1
1
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
Advanced parameter
CTSoft
Menu 0
PS
1
PS
1
PS
1
PS
Commander SK Advanced User Guide
Issue Number: 9
descriptions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents