Menu 12: Programmable Threshold And Variable Selector - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Menu 12
Introduction
x.00
10.13

Menu 12: Programmable threshold and variable selector

Table 10-24 Menu 12 parameters: single line descriptions
Parameter
12.01
Threshold detector 1 output
12.02
Threshold detector 2 output
12.03
Threshold detector 1 source
12.04
Threshold detector 1 level
12.05
Threshold detector 1 hysteresis
12.06
Threshold detector 1 output invert
12.07
Threshold detector 1 destination
12.08
Variable selector 1 source 1
12.09
Variable selector 1 source 2
12.10
Variable selector 1 mode
12.11
Variable selector 1 destination
12.12
Variable selector 1 output
12.13
Variable selector 1 source 1 scaling
12.14
Variable selector 1 source 2 scaling
12.15
Variable selector 1 control
12.16
Not used
12.17
Not used
12.18
Not used
12.19
Not used
12.20
Not used
12.21
Not used
12.22
Not used
12.23
Threshold detector 2 source
12.24
Threshold detector 2 level
12.25
Threshold detector 2 hysteresis
12.26
Threshold detector 2 output invert
12.27
Threshold detector 2 destination
12.28
Variable selector 2 source 1
12.29
Variable selector 2 source 2
12.30
Variable selector 2 mode
12.31
Variable selector 2 destination
12.32
Variable selector 2 output
12.33
Variable selector 2 source 1 scaling
12.34
Variable selector 2 source 2 scaling
12.35
Variable selector 2 control
12.36
Not used
12.37
Not used
12.38
Not used
12.39
Not used
The brake control functions are provided to allow well co-ordinated operation of an external brake with the drive. While both hardware
and software are designed to high standards of quality and robustness, they are not intended for use as safety functions, i.e. where a
fault or failure would result in a risk of injury. In any application where the incorrect operation of the brake release mechanism could
result in injury, independent protection devices of proven integrity must also be incorporated.
WARNING
12.40
Brake release indicator
12.41
Brake controller enable
12.42
Brake release current threshold
12.43
Brake apply current threshold
12.44
Brake release frequency
12.45
Brake apply frequency
12.46
Pre-brake release delay
12.47
Post-brake release delay
152
Parameter
Keypad and
description format
display
communications
{12}
{46}
{47}
{48}
{49}
{50}
{51}
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
RTU
programming
Range
OFF(0) or On(1)
OFF(0) or On(1)
Pr 0.00 to Pr 21.51
0.0 to 100.0%
0.0 to 25.0%
OFF(0) or On(1)
Pr 0.00 to Pr 21.51
Pr 0.00 to Pr 21.51
Pr 0.00 to Pr 21.51
0 to 9
Pr 0.00 to Pr 21.51
±100.0%
±4.000
±4.000
0.00 to 99.99
Pr 0.00 to Pr 21.51
0.0 to 100.0%
0.0 to 25.0%
OFF(0) or On(1)
Pr 0.00 to Pr 21.51
Pr 0.00 to Pr 21.51
Pr 0.00 to Pr 21.51
0 to 9
Pr 0.00 to Pr 21.51
±100.0%
±4.000
±4.000
0.00 to 99.99
OFF(0) or On(1)
diS(0), rEL(1), d IO(2),
USEr(3)
0 to 200%
0 to 200%
0.0 to 20.0 Hz
0.0 to 20.0 Hz
0.0 to 25.0 s
0.0 to 25.0 s
Advanced parameter
CTSoft
Menu 0
descriptions
Default
Setting
Pr 0.00
0.0
0.0
OFF(0)
Pr 0.00
Pr 0.00
Pr 0.00
0
Pr 0.00
1.000
1.000
0.00
Pr 0.00
0.0
0.0
OFF(0)
Pr 0.00
Pr 0.00
Pr 0.00
0
Pr 0.00
1.000
1.000
0.00
diS(0)
Edit mode exit
50%
10%
1.0
2.0
1.0
1.0
Commander SK Advanced User Guide
Issue Number: 9
Update Rate
21 ms
21 ms
Drive reset
21 ms
21 ms
21 ms
Drive reset
Drive reset
Drive reset
21 ms
Drive reset
21 ms
21 ms
21 ms
B
Drive reset
21 ms
21 ms
21 ms
Drive reset
Drive reset
Drive reset
21 ms
Drive reset
21 ms
21 ms
21 ms
B
21 ms
21 ms
21 ms
21 ms
21 ms
21 ms
21 ms