Analog Output Scaling; Current Loop Loss Indicator; Analog Input 1 Offset; Analog Output Control (Terminal B1) - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Parameter
Introduction
x.00
description format
NOTE
Users wanting to output load should be aware of the maximum values of the parameters they are routing to the output.
The maximum value of Pr 4.02 (active current) is the maximum level of current that the drive can operate at which is drive rating x 2. Therefore, at
rated load the analog output will be 1/2 x 10 = 5V.
Users wishing to see 10V output at 100% load will need to set Pr 7.19 to Pr 4.20 and Pr 4.24 = 100.
7.20

Analog output scaling

Bit
SP
Coding
Range
0.000 to 4.000
Default
1.000
Update rate
21 ms
This parameter can be used to scale the analog output if so desired. However in most cases it is not necessary as the output is automatically scaled
such that when the source parameter is at its maximum, the analog output will be at its maximum.
7.21 to 7.27
Unused parameters
7.28

Current loop loss indicator

Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
5 ms
If analog input 1 is programmed in any of the modes 2 to 5 (see Pr 7.06 on page 104) then this bit is set to On(1) if the current input falls below 3mA.
This bit can be designated to a digital output to indicate that the current input is less than 3mA.
7.29
Unused parameter
7.30

Analog input 1 offset

7.31
Analog input 2 offset
Bit
SP
Coding
Range
±100.0%
Default
0.0
Update rate
5 ms
An offset can be added to each analog input with a range from -100% to 100%. If the sum of the input and the offset exceeds ±100% the results is
limited to ±100%.
7.32
Unused parameter
7.33

Analog output control (Terminal B1) {36}

Bit
SP
Coding
Range
Fr(0), Ld(1), A(2), Por(3), USEr(4)
Default
Fr(0)
Update rate
Actioned on exit of edit mode
This offers a simple control of Pr 7.19 to change the analog output. Its function is used to set the value of Pr 7.19 between a frequency output, load
output, current output, or power output, or to leave the value unchanged. A user wishing to change the analog output to something other than these
must first program this parameter to USEr (or 4).
Pr 7.33
Display
0
Fr
1
Ld
2
A
3
Por
4
USEr
Commander SK Advanced User Guide
Issue Number: 9
Keypad and
Serial
display
communications
FI
DE
Txt VM DP ND
3
FI
DE
Txt VM DP ND
1
FI
DE
Txt VM DP ND
1
FI
DE
Txt VM DP ND
1
Function
Frequency output
Load output
Current output
Power output
Allows Pr 7.19 to be set up by user.
www.controltechniques.com
CT Modbus
PLC Ladder
RTU
programming
RA
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
Pr 7.19
Pr 2.01
Pr 4.02
Pr 4.01
Pr 5.03
Advanced parameter
CTSoft
Menu 0
descriptions
PS
1
1
PS
PS
1
PS
1
Menu 7
107