This source parameter and Pr 9.04 define the inputs for source 1 of the programmable logic functions.
Any valid parameter can be programmed into these inputs.
If one or both inputs to the logic function are invalid, then the logic output will always be 0.
9.15
Logic function 2 source 1 invert
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
21 ms
Setting this parameter and Pr 9.05 to On(1) causes the input sense of the logic functions to be inverted.
9.16
Logic function 2 source 2
Bit
SP
Coding
Range
Pr 0.00 to Pr 21.51
Default
Pr 0.00
Update rate
Read on drive reset
This source parameter and Pr 9.06 defines the inputs for source 2 of the programmable logic functions.
Any valid parameter can be programmed into these inputs.
If one or both inputs to the logic function are invalid, then the logic output will always be 0.
9.17
Logic function 2 source 2 invert
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
21 ms
Setting this parameter and Pr 9.07 to On(1) causes the input sense of the logic functions to be inverted.
9.18
Logic function 2 output invert
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
21 ms
Setting this parameter and Pr 9.08 to On(1) causes the output sense from the logic functions to be inverted.
9.19
Logic function 2 delay
Bit
SP
Coding
Range
±25.0 s
Default
0.0
Update rate
21 ms
If the delay parameter is positive, the delay ensures that the output does not become active until an active condition has been present at the input for