Pid Low Limit/Pid Scaling/Pid Output Destination; Pid Hold Integrator; Select Symmetrical Limit On Pid; Pid Main Reference - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Parameter
Introduction
x.00
description format
14.14
PID low limit
Bit
SP
Coding
Range
±100.0 %
Default
-100.0
Update rate
21 ms
If Pr 14.18 = OFF(0), the high limit (Pr 14.13) defines the maximum positive output for the PID controller and the lower limit (Pr 14.14) defines the
minimum positive or maximum negative output. If Pr 14.18 = On, the high limit defines the maximum positive or negative magnitude for the PID
controller output. When any of the limits are active the integrator is held.
14.15
PID scaling
Bit
SP
Coding
Range
0.000 to 4.000
Default
1.000
Update rate
21 ms
The PID output is scaled by this parameter before being added to the main reference. After the addition to the main reference, the output is
automatically scaled again to match the range of the destination parameter.
14.16
PID output destination
Bit
SP
Coding
Range
Pr 0.00 to Pr 21.51
Default
Pr 0.00
Update rate
Read on drive reset
The destination parameter should be set up with the parameter that the PID controller is to control. Only parameters which are not protected can be
controlled by the PID function. If a non valid parameter is programmed the output is not routed anywhere. If the PID is to control speed then it is
suggested that one of the preset speed parameters is entered here.
14.17

PID hold integrator

Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
21 ms
When this parameter is set to 0 the integrator operates normally. Setting this parameter to On(1) will cause the integrator value to be held as long as
the PID is enabled when the drive is disabled. Setting this parameter does not prevent the integrator from being reset to zero if the PID controller is
disabled.
14.18

Select symmetrical limit on PID

Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
21 ms
See Pr 14.13 and Pr 14.14 on page 151 and page 152 respectively.
14.19

PID main reference

Bit
SP
Coding
Range
±100.0%
Update rate
21 ms
This parameter monitors the main reference input of the PID controller.
Commander SK Advanced User Guide
Issue Number: 9
Keypad and
Serial
display
communications
FI
DE
Txt VM DP ND
1
FI
DE
Txt VM DP ND
3
FI
DE
Txt VM DP ND
1
2
FI
DE
Txt VM DP ND
FI
DE
Txt VM DP ND
FI
DE
Txt VM DP ND
1
1
www.controltechniques.com
CT Modbus
PLC Ladder
RTU
programming
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
1
RA
NC
NV
PT
US RW BU
1
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
Advanced parameter
CTSoft
Menu 0
descriptions
PS
1
PS
1
PS
1
PS
PS
PS
Menu 14
169