and when this parameter is On the reference is given by:
Pr 1.01 = SELECTED REFERENCE + Pr 1.04
1.10
Allow negative references {17}
Bit
SP
Coding
1
Default
OFF(0)
Update rate
Background
0: OFF Allow negative references disabled
1: On
Allow negative references enabled
Needs to be set if the user requires to change the direction of rotation with a negative reference. If it is not set, all negative references are treated as
zero. Possible negative references are:
Preset speeds 1 to 8
Keypad reference
Precision reference
Analog reference from I/O Solutions Module
Reference from a comms Solutions Module
NOTE
Both standard analog inputs are unipolar and setting this bit does not allow bipolar analog references to be applied to the drive. However, the I/O
Solutions Module has a bipolar input for this purpose.