Reference Enabled Indicator - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Menu 1
Introduction
x.00
1.11

Reference enabled indicator {91}

1.12
Reverse selected indicator
1.13
Jog selected indicator
Bit
SP
Coding
1
Update rate
2ms
These flags are controlled by the drive sequencer defined in Menu 6. They select the appropriate reference as commanded by the drive logic.
1.14
Reference selector
Bit
SP
Coding
Range
A1.A2(0), A1.Pr(1), A2.Pr(2), Pr(3), PAd(4), Prc(5)
Default
A1.A2(0)
Second motor
Pr 21.03
parameter
Update rate
5ms
This parameter is used to select a speed reference for motor 1 as follows:
0: A1.A2 Analog reference 1 or 2 selected by terminal input
1: A1.Pr Analog reference 1 (current) or 3 Presets selected by terminal input
2: A2.Pr Analog reference 2 (voltage) or 3 Presets selected by terminal input
3: Pr
4 Preset speeds selected by terminal input
4: PAd
Keypad reference selected
5: Prc
Precision reference selected
NOTE
For existing users of Commander SE:
On Commander SK, Pr 1.14 (Pr 21.03) is not automatically set-up for modes 1 to 3. Digital inputs need to be assigned to Pr 1.45 and Pr 1.46, to allow
selection of preset speeds. The tables below show possible configurations:
With Eur defaults
Terminal B4
Pr 1.14
Destination
A1.A2(0)
Pr 6.29
A1.Pr(1)
Pr 1.45
A2.Pr(2)
Pr 1.45
Pr(3)
Pr 1.45
PAd(4)
Prc(5)
With USA defaults
Terminal B4
Pr 1.14
Destination
A1.A2(0)
Pr 6.31
A1.Pr(1)
Pr 1.45
A2.Pr(2
Pr 1.45
Pr(3)
Pr 1.45
PAd(4)
Prc(5)
When this parameter is set to 0 the reference selected depends on the state of bit parameters Pr 1.41 to Pr 1.44. These bits are for control by digital
inputs such that references can be selected by external control. If any of the bits are set, the appropriate reference is selected (indicated by Pr 1.49).
If more than one bit is set the highest numbered will have priority.
In modes 1 and 2 a preset speed will be selected instead of the voltage or current selection if the preset selected is any preset speed other than
preset speed 1. This gives the user the flexibility to be able to select between current and 3 presets, or voltage and three presets, with only two digital
inputs.
NOTE
When Pr 1.14 is set to 5 (Prc), Pr 1.04, Pr 1.09 and Pr 1.38 cannot be used.
40
Parameter
Keypad and
description format
display
{92}
{93}
FI
DE
Txt VM DP
ND
1
FI
DE
Txt VM DP
ND
1
Terminal B7
Destination
Pr 1.41
Selected by terminal input
Pr 1.46
Pr 1.46
Pr 1.46
Terminal B7
Destination
Pr 1.41
Selected by terminal input
Pr 1.46
Pr 1.46
Pr 1.46
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
communications
RTU
programming
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
Pr 1.49
1
2
3
4
5
Pr 1.49
1
2
3
4
5
Advanced parameter
CTSoft
Menu 0
PS
PS
1
Commander SK Advanced User Guide
Issue Number: 9
descriptions