Boolean 16 To Integer Conversion B16I - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
13.7
13.7.1
13.7.2
Application manual
REFPDIF (87N)
I3PW1CT1
I3PW2CT1
I3P
FXDSIGN
GRP_OFF
ANSI11000084_1_en.vsd
ANSI11000084 V1 EN
Figure 174:
REFPDIF (87N) function inputs for normal transformer application

Boolean 16 to Integer conversion B16I

Identification
Function description
Boolean 16 to integer conversion
Application
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary
(logical) signals into an integer. It can be used – for example, to connect logical output
signals from a function (like distance protection) to integer inputs from another function
(like line differential protection). B16I does not have a logical node mapping.
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to
16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value according
to the table below from 0 to 32768. This follows the general formula: INx = 2
1≤x≤16. The sum of all the values on the activated INx will be available on the output
OUT as a sum of the values of all the inputs INx that are activated. OUT is an integer.
When all INx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer
65535 is available on the output OUT. B16I function is designed for receiving up to 16
IEC 61850
IEC 60617
identification
identification
B16I
-
Section 13
Logic
ANSI/IEEE C37.2
device number
-
x-1
where
389

Advertisement

Table of Contents
loading

Table of Contents