Interlocking For Breaker-And-A-Half Diameter Bh (3); Application - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
12.4.9
12.4.9.1
Application manual
If, in this case, line voltage supervision is added, then rather than setting 989 to open state,
specify the state of the voltage supervision:
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0

Interlocking for breaker-and-a-half diameter BH (3)

Application

The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half diameter
according to figure 166.
Section 12
Control
373