1MRK 505 337-UUS -
12.4.9
12.4.9.1
Application manual
If, in this case, line voltage supervision is added, then rather than setting 989 to open state,
specify the state of the voltage supervision:
•
989_OP = VOLT_OFF
•
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
•
VOLT_OFF = 1
•
VOLT_ON = 0
Interlocking for breaker-and-a-half diameter BH (3)
Application
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half diameter
according to figure 166.
Section 12
Control
373