Analog Input Signals - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 14
Monitoring
14.6.3.3
14.6.3.4
426
Func103N: Function type number (0-255) for binary input N according to
IEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection, 176:
transformer differential protection and 192: line differential protection.
Info103N: Information number (0-255) for binary input N according to IEC-60870-5-103,
that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.

Analog input signals

Up to 40 analog signals can be selected among internal analog and analog input signals.
PCM600 is used to configure the signals.
For retrieving remote data from LDCM module, the Disturbance report
function should not be connected to a 3 ms SMAI function block if this is
the only intended use for the remote data.
The analog trigger of Disturbance report is not affected if analog input M is to be included
in the disturbance recording or not (OperationM = Enabled/Disabled).
If OperationM = Disabled, no waveform (samples) will be recorded and reported in graph.
However, Trip value, pre-fault and fault value will be recorded and reported. The input
channel can still be used to trig the disturbance recorder.
If OperationM = Enabled, waveform (samples) will also be recorded and reported in
graph.
NomValueM: Nominal value for input M.
OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance report may
trig for high/low level of analog input M (Enabled) or not (Disabled).
OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative
nominal value for analog input M in percent of nominal value.
Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
Indications
IndicationMaN: Indication mask for binary input N. If set (Show), a status change of that
particular input, will be fetched and shown in the disturbance summary on local HMI. If
not set (Hide), status change will not be indicated.
SetLEDN: Set red LED on local HMI in front of the IED if binary input N changes status.