ABB REB670 Applications Manual page 457

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
Application manual
The slave number can be set to any value between 1 and 254. The communication
speed, can be set either to 9600 bits/s or 19200 bits/s.
RevPolarity: Setting for inverting the light (or not). Standard IEC 60870-5-103
setting is Enabled.
CycMeasRepTime: See I103MEAS function block for more information.
EventRepMode: Defines the mode for how events are reported. The event buffer size
is 1000 events.
Event reporting mode
If EventRepMode = SeqOfEvent, all GI and spontaneous events will be delivered in the
order they were generated by BSW. The most recent value is the latest value delivered. All
GI data from a single block will come from the same cycle.
If EventRepMode = HiPriSpont, spontaneous events will be delivered prior to GI event.
To prevent old GI data from being delivered after a new spontaneous event, the pending
GI event is modified to contain the same value as the spontaneous event. As a result, the
GI dataset is not time-correlated.
Settings from PCM600
I103USEDEF
For each input of the I103USEDEF function there is a setting for the information number
of the connected signal. The information number can be set to any value between 0 and
255. To get proper operation of the sequence of events the event masks in the event
function is to be set to ON_CHANGE. For single-command signals, the event mask is to
be set to ON_SET.
In addition there is a setting on each event block for function type. Refer to description of
the Main Function type set on the local HMI.
Commands
As for the commands defined in the protocol there is a dedicated function block with eight
output signals. Use PCM600 to configure these signals. To realize the
BlockOfInformation command, which is operated from the local HMI, the output
BLKINFO on the IEC command function block ICOM has to be connected to an input on
an event function block. This input must have the information number 20 (monitor
direction blocked) according to the standard.
Disturbance Recordings
For each input of the Disturbance recorder function there is a setting for the information
number of the connected signal. The function type and the information number can be set
to any value between 0 and 255. To get INF and FUN for the recorded binary signals there
are parameters on the disturbance recorder for each input. The user must set these
parameters to whatever he connects to the corresponding input.
Refer to description of Main Function type set on the local HMI.
Section 16
Station communication
451