Section 12
Control
326
QCBAY
SCILO
SCILO
ANSI05000116 V1 EN
Figure 122:
Signal flow between apparatus control function blocks
Accepted originator categories for PSTO
If the requested command is accepted by the authority, the value will change. Otherwise
the attribute blocked-by-switching-hierarchy is set in the cause signal. If the PSTO value
is changed during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in
Table 38:
Accepted originator categories for each PSTO
Permitted Source To Operate
0 = Off
1 = Local
2 = Remote
3 = Faulty
Table continues on next page
IEC 61850
SXCBR
SCSWI
SXCBR
SXCBR
SCSWI
SXSWI
Originator (orCat)
4,5,6
1,4,5,6
2,3,4,5,6
4,5,6
1MRK 505 337-UUS -
189
152
989
en05000116_ansi.vsd
Table 38