Figure 73:
Principle CT connections for the complete station
This summation type bus differential protection still has the same main CT requirements
as outlined in section "". Some of these are:
main CT ratio differences can be tolerated up to 10:1 (for example, 3000/5A CT can
be balanced against CT"s as low as 300/5)
different main CT ratios are compensated numerically by a parameter setting
main CT shall not saturate quicker than 2 ms ( refer to section
requirements regarding main CT knee-point voltage)
However, due to the summation principle this type of busbar protection scheme has the
following limitations:
LB
LX
IB1
IX1
52
52
A
B
C
N
N
IB2
IX2
CT2
. . .
IED
with 1A
CT inputs
Section 6
Differential protection
A-bus
A
B
C
N
Summation CTs
CT24
ANSI06000127_2_en.vsd
""
for detailed CT
151