Single Circuit Breaker With Double Busbar, Internal Voltage Selection - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 12
Control
12.1.3.3
290

Single circuit breaker with double busbar, internal voltage selection

Bus 1
Fuse
bus1 Voltage
VT
V REF 1
Fuse
bus2 Voltage
VT
V REF 2
lineVoltage /1/2/3
VA/VB/VC
ANSI10000095 V1 EN
Figure 111:
Connection of the SESRSYN function block in a single breaker, double
busbar arrangement with internal voltage selection
When internal voltage selection is needed, the voltage transformer circuit connections are
made according to figure 111. The voltage from the busbar 1 VT is connected to V3PB1
and the voltage from busbar 2 is connected to V3PB2. The voltage from the line VT is
connected to V3PL1. The positions of the disconnectors and VT fuses shall be connected
as shown in figure 111. The voltage selection parameter CBConfig is set to Double bus.
Bus 2
189
289
152
Fuse
VT
Line
1MRK 505 337-UUS -
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI10000095-1-en.vsd
Application manual