Identification - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
18.6.1
18.6.2
18.6.3
18.7
18.7.1
Application manual

Identification

Function description
Measured value expander block
Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and
VNMMXU), current and voltage sequence measurement functions (CMSQI and VMSQI)
and IEC 61850 generic communication I/O functions (MVGAPC) are provided with
measurement supervision functionality. All measured values can be supervised with four
settable limits, that is low-low limit, low limit, high limit and high-high limit. The measure
value expander block ( RANGE_XP) has been introduced to be able to translate the
integer output signal from the measuring functions to 5 binary signals, that is below low-
low limit, below low limit, normal, above high-high limit or above high limit. The output
signals can be used as conditions in the configurable logic.
Setting guidelines
There are no settable parameters for the measured value expander block function.
Parameter setting groups
Application
Six sets of settings are available to optimize IED operation for different power system
conditions. By creating and switching between fine tuned setting sets, either from the local
HMI or configurable binary inputs, results in a highly adaptable IED that can cope with a
variety of power system scenarios.
Different conditions in networks with different voltage levels require highly adaptable
protection and control units to best provide for dependability, security and selectivity
requirements. Protection units operate with a higher degree of availability, especially, if
the setting values of their parameters are continuously optimized according to the
conditions in the power system.
Operational departments can plan for different operating conditions in the primary
equipment. The protection engineer can prepare the necessary optimized and pre-tested
settings in advance for different protection functions. Six different groups of setting
IEC 61850
IEC 60617