Section 14
Monitoring
408
Measurement function application for a 380kV OHL
Single line diagram for this application is given in figure 176:
380kV Busbar
800/5 A
380kV 120V
/
kV
3
3
P
Q
380kV OHL
ANSI09000039 V1 EN
Figure 176:
Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated in
figure
176
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel PhaseAngleRef
using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
general settings as shown in table 41.
level supervision of active power as shown in table 42.
calibration parameters as shown in table 43.
IED
ANSI09000039-1-en.vsd
1MRK 505 337-UUS -
Application manual