Bay Control (Qcbay) - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
12.3.1.1
Application manual
4 = Not in use
5 = All
6 = Station
7 = Remote
PSTO = All, then it is no priority between operator places. All operator places are allowed
to operate.
According to IEC61850 standard the orCat attribute in originator category are defined in
Table 39
Table 39:
orCat attribute according to IEC61850
Value
Description
0
not-supported
1
bay-control
2
station-control
3
remote-control
4
automatic-bay
5
automatic-station
6
automatic-remote
7
maintenance
8
process

Bay control (QCBAY)

The Bay control (QCBAY) is used to handle the selection of the operator place per bay.
The function gives permission to operate from two main types of locations either from
Remote (for example, control centre or station HMI) or from Local (local HMI on the IED)
or from all (Local and Remote). The Local/Remote switch position can also be set to Off,
which means no operator place selected that is, operation is not possible either from local
or from remote.
For IEC 61850-8-1 communication, the Bay Control function can be set to discriminate
between commands with orCat station and remote (2 and 3). The selection is then done
through the IEC61850-8-1 edition 2 command LocSta.
QCBAY also provides blocking functions that can be distributed to different apparatuses
within the bay. There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
4,5,6
1,2,3,4,5,6
2,4,5,6
3,4,5,6
Section 12
Control
327

Advertisement