ABB REB670 Applications Manual page 411

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
Application manual
IGenZeroDb: Minimum level of current in % of IBase used as indication of zero current
(zero point clamping). If measured value is below IGenZeroDb calculated S, P, Q and PF
will be zero.
VMagCompY: Magnitude compensation to calibrate voltage measurements at Y% of Vn,
where Y is equal to 5, 30 or 100.
IMagCompY: Magnitude compensation to calibrate current measurements at Y% of In,
where Y is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of In, where Y
is equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase current measurement
(CMMXU).
IMagCompY: Magnitude compensation to calibrate current measurements at Y% of In,
where Y is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of In, where Y
is equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase voltage measurement
(VMMXU).
VMagCompY: Amplitude compensation to calibrate voltage measurements at Y% of Vn,
where Y is equal to 5, 30 or 100.
VAngCompY: Angle compensation to calibrate angle measurements at Y% of Vn, where
Y is equal to 5, 30 or 100.
The following general settings can be set for all monitored quantities included in the
functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X in setting
names below equals S, P, Q, PF, V, I, F, IA,IB,IC, VA, VB, VCVAB, VBC, VCA, I1, I2,
3I0, V1, V2 or 3V0.
Xmin: Minimum value for analog signal X set directly in applicable measuring unit.
Xmax: Maximum value for analog signal X.
XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.
Observe the related zero point clamping settings in Setting group N for CVMMXN
(VGenZeroDb and IGenZeroDb). If measured value is below VGenZeroDb and/or
IGenZeroDb calculated S, P, Q and PF will be zero and these settings will override
XZeroDb.
Section 14
Monitoring
405

Advertisement

Table of Contents
loading

Table of Contents