Section 12
Control
12.3.1.2
328
IEC13000016 V2 EN
Figure 123:
APC - Local remote function block
Switch controller (SCSWI)
SCSWI may handle and operate on one three-phase device or three one-phase switching
devices.
After the selection of an apparatus and before the execution, the switch controller
performs the following checks and actions:
•
A request initiates to reserve other bays to prevent simultaneous operation.
•
Actual position inputs for interlocking information are read and evaluated if the
operation is permitted.
•
The synchronism check/synchronizing conditions are read and checked, and
performs operation upon positive response.
•
The blocking conditions are evaluated
•
The position indications are evaluated according to given command and its requested
direction (open or closed).
1MRK 505 337-UUS -
IEC13000016-2-en.vsd
Application manual