Setting Guidelines - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
14.6.3
Application manual
If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder (record
made and fault number) and the fault locator information are available as GOOSE or
Report Control data. The same information is obtainable if IEC60870-5-103 is used.

Setting guidelines

The setting parameters for the Disturbance report function DRPRDRE are set via the local
HMI or PCM600.
It is possible to handle up to 40 analog and 352 binary signals, either internal signals or
signals coming from external inputs. The binary signals are identical in all functions that
is, Disturbance recorder (DR), Event recorder (ER), Indication (IND), Trip value recorder
(TVR) and Sequential of events (SOE) function.
User-defined names of binary and analog input signals is set using PCM600. The analog
and binary signals appear with their user-defined names. The name is used in all related
functions (Disturbance recorder (DR), Event recorder (ER), Indication (IND), Trip value
recorder (TVR) and Sequential of events (SOE)).
Figure
180
shows the relations between Disturbance report, included functions and
function blocks. Sequential of events (SOE), Event recorder (ER) and Indication (IND)
uses information from the binary input function blocks (BxRBDR). Trip value recorder
(TVR) uses analog information from the analog input function blocks (AxRADR),.
Disturbance report function acquires information from both AxRADR and BxRBDR.
Figure 180:
Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also influences the
sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick status
information about the IED.
Green LED:
Steady light
Flashing light
Dark
Yellow LED:
Steady light
Flashing light
Red LED:
Steady light
Flashing
In Service
Internal failure
No power supply
A Disturbance Report is triggered
The IED is in test mode
Triggered on binary signal N with
The IED is in configuration mode
Section 14
Monitoring
SetLEDN = Enabled
423