Example How To Connect Single-Phase Ct To The Ied - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 4
Analog inputs
A
B
Protected Object
ANSI11000028 V2 EN
Figure 25:
Delta DAC connected three-phase CT set
4.2.2.7
76
C
IA-IC
IB-IA
IC-IB
In this case, everything is done in a similar way as in the above described example, except
that for all used current inputs on the TRM the following setting parameters shall be
entered:
CT
=800A
prim
CT
=1A
sec
CTWyePoint=ToObject
ConnectionType=Ph-Ph
It is important to notice the references in SMAI. As inputs at Ph-Ph are expected to be A-
B, B-Crespectively C-A we need to tilt 180º by setting ToObject.

Example how to connect single-phase CT to the IED

Figure
26
gives an example how to connect the single-phase CT to the IED. It gives an
overview of the required actions by the user in order to make this measurement available
to the built-in protection and control functions within the IED as well.
IED
2
3
1MRK 505 337-UUS -
4
SMAI_20
ANSI11000028-2-en.vsd
Application manual