(status) of the result of the commands is supposed to be achieved by other means, such as
binary inputs and SPGGIO function blocks.
PSTO is the universal operator place selector for all control functions.
Even if PSTO can be configured to allow LOCAL or ALL operator
positions, the only functional position usable with the SPC8GAPC
function block is REMOTE.

Setting guidelines

The parameters for the single point generic control 8 signals (SPC8GAPC) function are
set via the local HMI or PCM600.
Operation: turning the function operation Enabled/Disabled.
There are two settings for every command output (totally 8):
Latchedx: decides if the command signal for output x is Latched (steady) or Pulsed.
tPulsex: if Latchedx is set to Pulsed, then tPulsex will set the length of the pulse (in
seconds).
AutomationBits, command function for DNP3.0
AUTOBITS

Identification

Function description
AutomationBits, command function for
DNP3

Application

Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in
order to get into the configuration the commands coming through the DNP3.0
protocol.The AUTOBITS function plays the same role as functions GOOSEBINRCV (for
IEC 61850) and MULTICMDRCV (for LON).AUTOBITS function block have 32
individual outputs which each can be mapped as a Binary Output point in DNP3. The
IEC 61850
IEC 60617
identification
identification
AUTOBITS
-
Section 12
Control
ANSI/IEEE C37.2
device number
-
379