Thermal Overload Protection, Two Time Constants Trpttr (49) - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
7.5
Application manual
Reverse
Area
ANSI10000031 V1 EN
Figure 89:
Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
VPolMin: Minimum polarization (reference) voltage % of VBase.
I>Dir: Operate residual current level for directional comparison scheme. The setting is
given in % of IBase. The pickup forward or pickup reverse signals can be used in a
communication scheme. The appropriate signal must be configured to the communication
scheme block.
Thermal overload protection, two time constants
TRPTTR (49)
AngleRCA
Forward
Area
Iop = I2
Section 7
Current protection
Vpol=-V2
ANSI10000031-1-en.vsd
197