Logical Signal Status Report Binstatrep - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 14
Monitoring
14.7
14.7.1
14.7.2
428
triggering is used, chose settings by a sufficient margin from normal operation values.
Phase voltages are not recommended for trigging.
Remember that values of parameters set elsewhere are linked to the information on a
report. Such parameters are, for example, station and object identifiers, CT and VT ratios.

Logical signal status report BINSTATREP

Identification
Function description
Logical signal status report
Application
The Logical signal status report (BINSTATREP) function makes it possible for a SPA
master to poll signals from various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and can
be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN
Figure 181:
BINSTATREP logical diagram
IEC 61850
IEC 60617
identification
identification
BINSTATREP
t
IEC09000732-1-en.vsd
1MRK 505 337-UUS -
ANSI/IEEE C37.2
device number
-
-
t
Application manual