Application - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 13
Logic
13.10.2
394

Application

Integer to boolean 16 conversion with logic node representation function (ITBGAPC) is
used to transform an integer into a set of 16 boolean signals. ITBGAPC function can
receive an integer from a station computer – for example, over IEC 61850–8–1. This
function is very useful when the user wants to generate logical commands (for selector
switches or voltage controllers) by inputting an integer number. ITBGAPC function has
a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535 communicated via
IEC61850 and connected to the ITBGAPC function block to a combination of activated
outputs OUTx where 1≤x≤16.
The values of the different OUTx are according to the Table 40.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
Table 40:
Output signals
Name of OUTx
Type
OUT1
BOOLEAN
OUT2
BOOLEAN
OUT3
BOOLEAN
OUT4
BOOLEAN
OUT5
BOOLEAN
OUT6
BOOLEAN
OUT7
BOOLEAN
OUT8
BOOLEAN
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16) are
active equals 65535. This is the highest integer that can be converted by the ITBGAPC
function block.
Description
Value when
activated
Output 1
1
Output 2
2
Output 3
4
Output 4
8
Output 5
16
Output 6
32
Output 7
64
Output 8
128
Output 9
256
Output 10
512
Output 11
1024
Output 12
2048
Output 13
4096
Output 14
8192
Output 15
16384
Output 16
32768
1MRK 505 337-UUS -
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Application manual