Running hour-meter TEILGAPC

Identification
Function Description
Running hour-meter
Application
The function is used for user-defined logics and it can also be used for different purposes
internally in the IED. An application example is to accumulate the total running/energized
time of the generator, transformer, reactor, capacitor bank or even line.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed to 99999.9 hours. At overflow the accumulated time resets and the
accumulation starts from zero again.
Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in hours. The achievable
resolution of the settings is 0.1 hours (6 minutes).
tAlarm and tWarning are independent settings, that is, there is no check if
tAlarm > tWarning.
The limit for the overflow supervision is fixed at 99999.9 hours.
The setting tAddToTime is a user settable time parameter in hours.
IEC 61850
IEC 60617
identification
identification
TEILGAPC
-
1MRK 505 337-UUS -
ANSI/IEEE C37.2 device
number
-
Application manual