Example How To Connect The Open Delta Vt To The Ied For Low Impedance Grounded Or Solidly Grounded Power Systems - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.3.6
86
Example how to connect the open delta VT to the IED for low impedance
grounded or solidly grounded power systems
Figure
31
gives an example about the connection of an open delta VT to the IED for low
impedance grounded or solidly grounded power systems. It shall be noted that this type of
VT connection presents secondary voltage proportional to 3V
In case of a solid ground fault close to the VT location the primary value of 3Vo will be
equal to:
V
=
=
-
3
Vo
Ph Ph
V
-
Ph Gnd
3
EQUATION1927-ANSI V1 EN
The primary rated voltage of such VT is always equal to VPh-Gnd. Therefore, three series
connected VT secondary windings will give the secondary voltage equal only to one
individual VT secondary winding rating. Thus the secondary windings of such open delta
VTs quite often has a secondary rated voltage close to rated phase-to-phase VT secondary
voltage, that is, 115V or 115/√3V as in this particular example. Figure
overview of the actions which are needed to make this measurement available to the built-
in protection and control functions within the IED.
1MRK 505 337-UUS -
to the IED.
0
(Equation 7)
31
gives an
Application manual