Single circuit breaker with double busbar, external voltage selection

Bus 1
Fuse
VT
bus Voltage
VREF1
Voltag
Line
e
V
VA/VB/
C
ANSI10000094 V1 EN
Figure 110:
Connection of SESRSYN (25) function block in a single breaker, double
busbar arrangement with external voltage selection
In this type of arrangement no internal voltage selection is required. The voltage selection
is made by external relays typically connected according to figure 110. Suitable voltage
and VT fuse failure supervision from the two busbars are selected based on the position of
the busbar disconnectors. This means that the connections to the function block will be the
same as for the single busbar arrangement. The voltage selection parameter CBConfig is
set to No voltage sel.
Bus 2
Fuse
VT
189
289
152
1/2/3
Fuse
VT
Line
Section 12
Control
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI10000094-1-en.vsd
289