Section 18
Basic IED functions
472
Examples of adaptive frequency tracking
Preprocessing block shall only be used to feed functions within the same
execution cycles (e.g. use preprocessing block with cycle 1 to feed
transformer differential protection). The only exceptions are
measurement functions (CVMMXN, CMMXU,VMMXU, etc.) which
shall be fed by preprocessing blocks with cycle 8.
When two or more preprocessing blocks are used to feed one protection
function (e.g. over-power function GOPPDOP), it is of outmost
importance that parameter setting DFTReference has the same set value
for all of the preprocessing blocks involved
1MRK 505 337-UUS -