ABB REB670 Applications Manual page 263

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
Application manual
Table 35:
Available selection for current quantity within CVGAPC function
Set value for parameter
"CurrentInput"
PhaseA
1
2
PhaseB
PhaseC
3
4
PosSeq
NegSeq
5
3 · ZeroSeq
6
MaxPh
7
MinPh
8
9
UnbalancePh
PhaseA - PhaseB
10
PhaseB - PhaseC
11
PhaseC - PhaseA
12
MaxPh-Ph
13
14
MinPh-Ph
UnbalancePh-Ph
15
The user can select, by a setting parameter VoltageInput, to measure one of the following
voltage quantities shown in table 36.
Multipurpose protection
Comment
CVGAPC function will measure the phase A current phasor
CVGAPC function will measure the phase B current phasor
CVGAPC function will measure the phase C current phasor
CVGAPC function will measure internally calculated positive
sequence current phasor
CVGAPC function will measure internally calculated negative
sequence current phasor
CVGAPC function will measure internally calculated zero sequence
current phasor multiplied by factor 3
CVGAPC function will measure current phasor of the phase with
maximum magnitude
CVGAPC function will measure current phasor of the phase with
minimum magnitude
CVGAPC function will measure magnitude of unbalance current,
which is internally calculated as the algebraic magnitude difference
between the current phasor of the phase with maximum magnitude
and current phasor of the phase with minimum magnitude. Phase
angle will be set to 0° all the time
CVGAPC function will measure the current phasor internally
calculated as the vector difference between the phase A current
phasor and phase B current phasor (VA-VB)
CVGAPC function will measure the current phasor internally
calculated as the vector difference between the phase B current
phasor and phase C current phasor (VB-VC)
CVGAPC function will measure the current phasor internally
calculated as the vector difference between the phase C current
phasor and phase A current phasor ( VC-VA)
CVGAPC function will measure ph-ph current phasor with the
maximum magnitude
CVGAPC function will measure ph-ph current phasor with the
minimum magnitude
CVGAPC function will measure magnitude of unbalance current,
which is internally calculated as the algebraic magnitude difference
between the ph-ph current phasor with maximum magnitude and ph-
ph current phasor with minimum magnitude. Phase angle will be set
to 0° all the time
Section 10
257

Advertisement

Table of Contents
loading

Table of Contents