Section 12
Control
12.5.3
12.6
12.6.1
12.6.2
376
the number of positions of the switch can be established by settings (see below), one must
be careful in coordinating the settings with the configuration (if one sets the number of
positions to x in settings – for example, there will be only the first x outputs available from
the block in the configuration). Also the frequency of the (UP or DOWN) pulses should
be lower than the setting tPulse.
From the local HMI, the selector switch can be operated from Single-line diagram (SLD).

Setting guidelines

The following settings are available for the Logic rotating switch for function selection
and LHMI presentation (SLGAPC) function:
Operation: Sets the operation of the function Enabled or Disabled.
NrPos: Sets the number of positions in the switch (max. 32).
OutType: Steady or Pulsed.
tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).
tDelay: The delay between the UP or DOWN activation signal positive front and the
output activation.
StopAtExtremes: Sets the behavior of the switch at the end positions – if set to Disabled,
when pressing UP while on first position, the switch will jump to the last position; when
pressing DOWN at the last position, the switch will jump to the first position; when set to
Enabled, no jump will be allowed.

Selector mini switch VSGAPC

Identification

Function description
Selector mini switch

Application

Selector mini switch (VSGAPC) function is a multipurpose function used in the
configuration tool in PCM600 for a variety of applications, as a general purpose switch.
IEC 61850
IEC 60617
identification
identification
VSGAPC
-
1MRK 505 337-UUS -
ANSI/IEEE C37.2
device number
-
Application manual