Synchronism Check - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 12
Control
12.1.2.2
282
synchronism check is used and the value of FreqDiffMin must thus be identical to the
value FreqDiffM resp FreqDiffA for synchronism check function. The bus and line
frequencies must also be within a range of +/- 5 Hz from the rated frequency. When
the synchronizing option is included also for autoreclose there is no reason to have
different frequency setting for the manual and automatic reclosing and the frequency
difference values for synchronism check should be kept low.
The frequency rate of change is less than set value for both V-Bus and V-Line.
The closing angle is decided by the calculation of slip frequency and required pre-
closing time.
The synchronizing function compensates for measured slip frequency as well as the
circuit breaker closing delay. The phase angle advance is calculated continuously. Closing
angle is the change in angle during the set breaker closing operate time tBreaker.
The reference voltage can be phase-neutral A, B, C or phase-phase A-B, B-C, C-A or
positive sequence (Require a three phase voltage, that is VA, VB and VC) . By setting the
phases used for SESRSYN, with the settings SelPhaseBus1, SelPhaseBus2,
SelPhaseLine2 and SelPhaseLine2, a compensation is made automatically for the voltage
amplitude difference and the phase angle difference caused if different setting values are
selected for the two sides of the breaker. If needed an additional phase angle adjustment
can be done for selected line voltage with the PhaseShift setting.

Synchronism check

The main purpose of the synchronism check function is to provide control over the closing
of circuit breakers in power networks in order to prevent closing if conditions for
synchronism are not detected. It is also used to prevent the re-connection of two systems,
which are divided after islanding and after a three pole reclosing.
Single pole auto-reclosing does not require any synchronism check since
the system is tied together by two phases.
SESRSYN (25) function block includes both the synchronism check function and the
energizing function to allow closing when one side of the breaker is dead. SESRSYN (25)
function also includes a built in voltage selection scheme which allows adoption to
various busbar arrangements.
1MRK 505 337-UUS -
Application manual