Section 16
Station communication
16.2.6.3
440
Setting guidelines
Redundant communication (DUODRV) is configured in the local HMI under Main
menu/Settings/General settings/Communication/Ethernet configuration/Rear
OEM - Redundant PRP
The settings can then be viewed, but not set, in the Parameter Setting tool in PCM600
under Main menu/IED Configuration/Communication/Ethernet configuration/
DUODRV:
Operation: The redundant communication will be activated when this parameter is set to
On.After confirmation the IED will restart and the setting alternatives Rear OEM - Port
AB and CD will not be further displayed in the local HMI. The ETHLANAB and
ETHLANCD in the Parameter Setting Tool are irrelevant when the redundant
communication is activated, only DUODRV IPAdress and IPMask are valid.
1MRK 505 337-UUS -
Application manual