Horizontal Communication Via Goose For Interlocking Gooseintlkrcv - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
16.2.2
Table 46:
GOOSEINTLKRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
16.2.3
16.2.4
Application manual
Station HSI
MicroSCADA
GOOSE
IED
IED
A
A
Control
Protection
IEC05000734 V1 EN
Figure 184:
Example of a broadcasted GOOSE message
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV
Unit
Step
-
-
Setting guidelines
There are two settings related to the IEC 61850–8–1 protocol:
Operation User can set IEC 61850 communication to Enabled or Disabled.
GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send and received.
Generic communication function for Single Point indication
SPGAPC, SP16GAPC
Station communication
IED
IED
A
A
Control and protection
Control
Default
Description
Disabled
Operation Disabled/Enabled
Section 16
Gateway
IED
A
Protection
en05000734.vsd
437