Boolean 16 To Integer Conversion B16I; Identification - ABB REB650 Applications Manual

Relion 650 series, busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

Section 11
Logic
11.8
11.8.1
186
Example for use of GRP_OFF signal in FXDSIGN
The Restricted earth fault function (REFPDIF) can be used both for auto-
transformers and normal transformers.
When used for auto-transformers, information from both windings parts, together
with the neutral point current, needs to be available to the function. This means that
three inputs are needed.
REFPDIF
I3PW1CT1
I3PW2CT1
I3P
IEC09000619_3_en.vsd
IEC09000619 V3 EN-US
Figure 66:
REFPDIF function inputs for autotransformer application
For normal transformers only one winding and the neutral point is available. This
means that only two inputs are used. Since all group connections are mandatory to
be connected, the third input needs to be connected to something, which is the
GRP_OFF signal in FXDSIGN function block.
FXDSIGN
GRP_OFF
IEC09000620_3_en.vsd
IEC09000620 V3 EN-US
Figure 67:
REFPDIF function inputs for normal transformer application

Boolean 16 to Integer conversion B16I

Identification

Function description
Boolean 16 to integer conversion
REFPDIF
I3PW1CT1
I3PW2CT1
I3P
IEC 61850
identification
B16I
1MRK 505 388-UEN B
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Busbar protection REB650 2.2 IEC
Application manual
SEMOD175715-1 v1
SEMOD175721-2 v2