ABB REB670 Applications Manual page 417

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
Application manual
132kV Busbar
200/5
31.5 MVA
P
500/5
33kV Busbar
ANSI09000040 V1 EN
Figure 177:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 177, it is necessary
to do the following:
1.
Set correctly all CT and VT and phase angle reference channel PhaseAngleRef data
using PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to LV side CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the
following table 44:
IED
Q
V
AB
33kV 120V
/
3
3
ANSI09000040-1-en.vsd
Section 14
Monitoring
411