Boolean 16 To Integer Conversion With Logic Node Representation Btigapc - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 13
Logic
13.8
390
booleans input locally. If the BLOCK input is activated, it will freeze the output at the last
value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT
on the function block B16I.
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
IN14
BOOLEAN
IN15
BOOLEAN
IN16
BOOLEAN
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16)
are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to
an integer by the B16I function block.
Boolean 16 to Integer conversion with logic node
representation BTIGAPC
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
0
Input 11
0
Input 12
0
Input 13
0
Input 14
0
Input 15
0
Input 16
1MRK 505 337-UUS -
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
1024
0
2048
0
4096
0
8192
0
16384
0
32768
0
Application manual