Function and information types
Product type IEC103mainFunType value Comment:
REL 128 Compatible range
REC 242 Private range, use default
RED 192 Compatible range
RET 176 Compatible range
REB 207 Private range
REG 150 Private range
REQ 245 Private range
RES 118 Private range
Refer to the tables in the Technical reference manual /Station communication, specifying
the information types supported by the communication protocol IEC 60870-5-103.
To support the information, corresponding functions must be included in the protection
IED.
There is no representation for the following parts:
Generating events for test mode
Cause of transmission: Info no 11, Local operation
Glass or plastic fibre should be used. BFOC/2.5 is the recommended interface to use
(BFOC/2.5 is the same as ST connectors). ST connectors are used with the optical power
as specified in standard.
For more information, refer to IEC standard IEC 60870-5-103.
ACC
88
89
90
91
92
93
94
95
Section 16
Station communication
IEC103 meaning
Private range
Private range
Private range
Private range
Private range
Private range
Private range
Private range