Busbar protection REB670
Pre-configured
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REB670

  • Page 1 ® Relion 670 series Busbar protection REB670 Pre-configured Product Guide...
  • Page 2: Table Of Contents

    16. Ordering..............54 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.
  • Page 3: Application

    T-connections and meshed directly in primary amperes. The operating slope for the corners. REB670 can be used for protection of single and differential operating characteristic is fixed to 53% in the double busbar with or without transfer bus, double circuit algorithm.
  • Page 4 Three configurations have been made available for pre- refurbishment of existing installations. configured REB670 IED. It shall be noted that all three configurations include the following features: Description of 3 ph package A20...
  • Page 5 This configuration is available for it can be used for double busbar-single breaker stations only three REB670 variants (that is A31, B21 and B31). where disconnector replica is done by using just b auxiliary contact from every disconnector and/or circuit Application examples of REB670 breakers.
  • Page 6 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 xx06000013.vsd IEC06000013 V1 EN Figure 4. Example of single bus station with transfer bus QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 xx06000014.vsd IEC06000014 V1 EN Figure 5.
  • Page 7 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 xx06000017.vsd IEC06000017 V1 EN Figure 8. Example of one-and-a-half breaker station xx06000018.vsd IEC06000018 V1 EN Figure 9. Example of double bus-double breaker station QB12 QB11 QB41 QB21 QB42 QB22 QB31 QB32 xx06000019.vsd...
  • Page 8 Product version: 1.2 Note that customized REB670 is delivered without any configuration. Thus the complete IED engineering shall be done by the customer or its system integrator. In order to secure proper operation of the busbar protection it is strictly recommended to always start engineering work from the PCM600 project for the pre-configured REB670 which is the closest to the actual application.
  • Page 9: Available Functions

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 2. Available functions Main protection functions = number of basic instances 3-A03 = optional function included in packages A03 (refer to ordering details) IEC 61850 ANSI Function description Busbar Differential protection...
  • Page 10 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Busbar Control SMBRREC Autorecloser 2-H05 2-H05 2-H05 2-H05 2-H05 QCBAY Apparatus control LOCREM Handling of LRswitch positions LOCREMCTR LHMI control of PSTO...
  • Page 11 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Designed to communicate IEC 61850 ANSI Function description Busbar Station communication SPA communication protocol LON communication protocol IEC60870-5-103 communication protocol 20/1 20/1 20/1 20/1 20/1 Operation selection between SPA and IEC60870-5-103 for SLM DNP3.0 for TCP/IP and EIA-485 communication protocol...
  • Page 12: Differential Protection

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup Parameter setting groups...
  • Page 13: Zone Selection

    Sensitive differential level BZISGGIO sensitive, even to a lower value than the maximum CT primary Differential protection zones in REB670 include a sensitive rating in the station. At detection of problems in CT operational level. This sensitive operational level is designed...
  • Page 14 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 these disconnectors then actually determine which CT input Note that the first scheme only requires fast breaking normally (that is, bay) is connected to which differential protection closed auxiliary contact (that is, b contact) for proper zone.
  • Page 15 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 • Permanently connect this bay current to zone A (that is, The third option ensures that the feeder, which is out of service, is not connected to any of the two zones during zone •...
  • Page 16: Current Protection

    In 6. Control order to utilize this functionality the circuit breaker status and CB closing command must be connected to the REB670. Autorecloser SMBRREC One of the overcurrent steps can be set and configured to act The autoreclosing function provides high-speed and/or as end-fault protection in REB670.
  • Page 17: Logic

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 those parts of the logic configuration that do not need controls if the block's output should reset or return to the extensive command receiving functionality (for example, state it was, after a power interruption. RESET input has SCSWI).
  • Page 18 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 A disturbance is defined as an activation of an input to the Trip value recorder DRPRDRE AxRADR or BxRBDR function blocks, which are set to trigger Information about the pre-fault and fault values for currents the disturbance recorder.
  • Page 19: Basic Ied Functions

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Measured value expander block RANGE_XP The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU), current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are provided with measurement supervision functionality.
  • Page 20: Station Communication

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 IEC06000192 V1 EN IEC06000191 V1 EN Figure 13. Example of status of primary switchgear objects Figure 12. Bay to zone connection example 1 User settable switchgear names 1 User settable bay name...
  • Page 21: Remote Communication

    SPA communication protocol signals only, up to 192 binary signals can be exchanged A single glass or plastic port is provided for the ABB SPA between two IEDs. For example, this functionality can be protocol. This allows extensions of simple substation...
  • Page 22 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 The two high speed signal output channels are used for communication port. The RS485 is a balanced serial applications where short operating time is essential. Eight communication that can be used either in 2-wire or 4-wire optically isolated binary inputs cater for required binary input connections.
  • Page 23 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 xx05000004.vsd IEC05000004 V1 EN Figure 15. Side-by-side mounting Case size 6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7 6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0 6U, 1/1 x 19”...
  • Page 24: Connection Diagrams

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 14. Connection diagrams Table 2. Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X51 and X52...
  • Page 25 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 4. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM and X132 X301:A, B, C, D...
  • Page 26 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 1MRK002801-AC-10-670-1.2-PG V1 EN Figure 16. Transformer input module (TRM) ■ Indicates high polarity CT/VT-input designation according to figure AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12 12I, 1A 12I, 5A Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-processing function blocks.
  • Page 27 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 1MRK002801-AC-15-670-1.2-PG V1 EN Figure 18. mA input module (MIM) 1MRK002801-AC-11-670-1.2-PG V1 EN Figure 17. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, and so on, and input contacts named XB to rear position X32, X42, and so on.
  • Page 28 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 1MRK002801-AC-7-670-1.2-PG V1 EN Figure 20. Power supply module (PSM) 1MRK002801-AC-12-670-1.2-PG V1 EN Figure 21. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output...
  • Page 29 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 1MRK002801-AC-13-670-1.2-PG V1 EN Figure 22. Static output module (SOM) 1MRK002801-AC-14-670-1.2-PG V1 EN Figure 23. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts...
  • Page 30: Technical Data

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 15. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the...
  • Page 31 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Binary inputs and outputs Table 8. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ± 20% 110/125 V RL ±...
  • Page 32 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 10. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ± 20% 110/125 V RL ± 20% 220/250 V RL ±...
  • Page 33 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 12. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs...
  • Page 34 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 14. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC Number of outputs Test voltage across open contact, 1 min...
  • Page 35 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 17. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% /%...
  • Page 36 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Type tests according to standards Table 19. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-22-1 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
  • Page 37 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 21. Environmental tests Test Type test value Reference standard Cold test Test Ad for 16 h at -25°C IEC 60068-2-1 Storage test Test Ad for 16 h at -40°C IEC 60068-2-1 Dry heat test Test Bd for 16 h at +70°C...
  • Page 38 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Differential protection Table 24. Busbar differential protection Function Range or value Accuracy Operating characteristic S=0.53 fixed ± 2.0% of I for I < I ± 2.0% of I for I > I Reset ratio >...
  • Page 39 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Current protection Table 25. Four step phase overcurrent protection OC4PTOC Function Setting range Accuracy lBase Operate current (5-2500)% of ± 1.0% of I at I ≤ I ± 1.0% of I at I > I...
  • Page 40 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 27. Breaker failure protection CCRBRF Function Range or value Accuracy Operate phase current (5-200)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio, phase current >...
  • Page 41: Smbrrec

    Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Control Table 29. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 1Ph (0.000-60.000) s ± 0.5% ± 10 ms...
  • Page 42 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Logic Table 30. Configurable logic blocks Logic block Quantity with update rate Range or value Accuracy fast medium normal LogicAND LogicOR LogicXOR LogicInverter LogicSRMemory LogicRSMemory LogicGate LogicTimer (0.000–90000.000) s ± 0.5% ± 10 ms LogicPulseTimer (0.000–90000.000) s...
  • Page 43 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Monitoring Table 31. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Connected current (0.2-4.0) × I ± 0.5% of I at I £ I ± 0.5% of I at I > I Table 32.
  • Page 44 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 36. Voltage sequence measurement VMSQI Function Range or value Accuracy Voltage positive sequence, U1 (10 to 300) V ± 0.3% of U at U ≤ 50 V ± 0.2% of U at U > 50 V...
  • Page 45 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 40. Indications Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances Table 41. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report...
  • Page 46 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Station communication Table 44. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 608–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
  • Page 47 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 49. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fibre: type ST Plastic fibre: type HFBR snap-in Fibre, optical budget Glass fibre: 11 dB (3000ft/1000 m typically *)
  • Page 48 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Remote communication Table 52. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fibre Graded-index Singlemode 9/125 µm Singlemode 9/125 µm...
  • Page 49 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Hardware Table 53. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 54. Water and dust protection level according to IEC 60529...
  • Page 50 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Basic IED functions Table 58. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 59. Time synchronization, time tagging...
  • Page 51 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 62. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp – high level...
  • Page 52 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Inverse characteristic Table 63. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø...
  • Page 53 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Table 64. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø EQUATION1251-SMALL V1 EN...
  • Page 54 To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: REB670*1.2-A20X01-C06-X0-A-A-B-A-A2-X0-CAX-XXX-XD. Using the code of each position #1-12 specified as REB670*1-2 2-3 3 3-4-5-6-7 7-8-9 9 9-10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12...
  • Page 55 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 First local HMI user dialogue language Notes and Rules HMI language, English IEC HMI language, English US Additional local HMI user dialogue language HMI language, German HMI language, Russian HMI language, French...
  • Page 56 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Binary input/output module, mA and time synchronization Notes and Rules boards. Note: 1BIM and 1 BOM included. Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 57 Please refer to the available functions table for included application functions. Accessories External current transformer unit Note: Only for REB670 B20, B21 and B31 3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 1/1 A Quantity: 1MRK 000 643-EA 3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 5/1 A...
  • Page 58 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 Interface converter (for remote end data communication) External interface converter from C37.94 to G703 Quantity: 1MRK 002 245-AA External interface converter from C37.94 to G703.E1 Quantity: 1MRK 002 245-BA Test switch contacts.
  • Page 59 Busbar protection REB670 1MRK505212-BEN E Pre-configured Product version: 1.2 LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA Manuals Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference manual, Installation and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label template is always included for each IED.
  • Page 60 670 series SPA and signal list 1MRK 500 092-WEN IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN Engineering manual 670 series 1MRK 511 240-UEN Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 62 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...