Elapsed Time Integrator With Limit Transgression And Overflow Supervision Teigapc - ABB REB670 Applications Manual

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 337-UUS -
13.11
13.11.1
13.11.2
13.11.3
Application manual
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
Identification
Function Description
Elapsed time integrator
Application
The function TEIGAPC is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is the integration of elapsed time
during the measurement of neutral point voltage or neutral current at earth-fault
conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed to 999999.9 seconds.
Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
If the values are above this range the resolution becomes lower
99 999.99 seconds ≤ tAlarm ≤ 999 999.9 seconds
99 999.99 seconds≤ tWarning ≤ 999 999.9 seconds
Note that tAlarm and tWarning are independent settings, that is, there is no
check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 999999.9 seconds.
IEC 61850
IEC 60617
identification
identification
TEIGAPC
-
Section 13
Logic
ANSI/IEEE C37.2 device
number
-
395