Section 16
Station communication
16.2.4.1
16.2.4.2
16.2.5
16.2.5.1
16.2.5.2
16.2.6
16.2.6.1
438

Application

Generic communication function for Measured Value (SPGAPC) function is used to send
one single logical output to other systems or equipment in the substation. It has one visible
input, that should be connected in ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC. However, PCM600 must be used
to get the signals sent by SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for Measured Value MVGAPC function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an analog
value and to permit measurement supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value
(MVGAPC) function allows the user to choose a deadband and a zero deadband for the
monitored signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and
low-low ranges of the measured value. The actual range of the measured value is shown
on the range output of MVGAPC function block. When a Measured value expander block
(RANGE_XP) is connected to the range output, the logical outputs of the RANGE_XP are
changed accordingly.
IEC 61850-8-1 redundant station bus communication
Identification
Function description
LHMI and ACT
identification
Parallel Redundancy
PRPSTATUS
Protocol Status
Duo driver
PRP
configuration
IEC 61850
IEC 60617
identification
identification
RCHLCCH
-
-
-
1MRK 505 337-UUS -
ANSI/IEEE C37.2
device number
-
-
Application manual