ABB REB670 Applications Manual page 72

Busbar protection 2.1 ansi, relion 670 series
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

Section 4
Analog inputs
ANSI06000196 V1 EN
Figure 19:
Example how to set CT_WyePoint parameters in the IED
66
For busbar protection it is possible to set the CT_WyePoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT inputs
marked with 1 in figure 19, set CT_WyePoint = ToObject, and for all CT inputs marked
with 2 in figure 19, set CT_WyePoint = FromObject.
The second solution will be to use all connected bays as reference objects. In that case for
all CT inputs marked with 1 in figure 19, set CT_WyePoint = FromObject, and for all CT
inputs marked with 2 in figure 19, set CT_WyePoint = ToObject.
Busbar
Busbar
Protection
1
2
1MRK 505 337-UUS -
2
1
en06000196_ansi.vsd
Application manual