Section 16
Station communication
16.5
16.5.1
446

IEC 60870-5-103 communication protocol

Application
Station
HSI
Star coupler
IED
IED
ANSI05000660 V4 EN
Figure 189:
Example of IEC 60870-5-103 communication structure for a substation
automation system
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must have
software that can interpret the IEC 60870-5-103 communication messages.
When communicating locally in the station using a Personal Computer (PC) or a Remote
Terminal Unit (RTU) connected to the Communication and processing module, the only
hardware needed is optical fibres and an opto/electrical converter for the PC/RTU, or a
RS-485 connection depending on the used IED communication interface.
Functionality
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system. In IEC terminology a
primary station is a master and a secondary station is a slave. The communication is based
on a point-to-point principle. The master must have software that can interpret the IEC
60870-5-103 communication messages. For detailed information about IEC
60870-5-103, refer to IEC60870 standard part 5: Transmission protocols, and to the
section 103, Companion standard for the informative interface of protection equipment.