Application manual
specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, except in the
following cases:
989_EX2 and 989_EX4 in modules BH_LINE_A and BH_LINE_B
152_EX3 in module AB_TRAFO
when they are set to 0=FALSE.

Interlocking for line bay ABC_LINE (3)

Application

The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 128. The function
can also be used for a double busbar arrangement without transfer busbar or a single
busbar arrangement with/without transfer busbar.
289
189
189G
152
289G
989
ANSI04000478 V1 EN
Figure 128:
Switchyard layout ABC_LINE (3)
The signals from other bays connected to the module ABC_LINE (3) are described below.

Signals from bypass busbar

To derive the signals:
WA1 (A)
WA2 (B)
WA7 (C)
789
989G
en04000478_ansi.vsd
Section 12
Control
339